High socket for tv

ok thanks so spuring off the shower is a no no. Im an electrical maintenance ina factory and was just always told its ok the spur off something bigger as long as protected with a fuse. Must be different for houses.

Thanks everyone

In many cases you can spur off something bigger, such as running lights off a socket circuit, via fused spur.

However, some circuits are designed to be 'dedicated' circuits.
 
is the problem the shower circuit? I no its a 40 Amp fuse in the CU thats why i thought it would be ok to take a 13A spur from the shower
 
is the problem the shower circuit? I no its a 40 Amp fuse in the CU thats why i thought it would be ok to take a 13A spur from the shower

Which will probably need all of those available 40 Amps when in use - if it's a 9kW shower or larger.
 