An awful lot of circuits for a terrace house.
And one not-matching old style. Doesn't that look lovely?An awful lot of circuits for a terrace house. I guess it has been rewired?
A recent wylex that. (having NSX)
Protecting the cable, not the appliance. It's gonna be in 2.5mm² so no worries20A for boiler and alarm ?
The Wylex unit that is pictured does meet the requirements of BS7671. It has been installed with two RCDs with a number of MCBs on each RCD. With this design, the problem (as you know) is that a fault on one sub-circuit takes out half of the installation. As above, this arrangement does meet the requirements of the regs.
If thje specification was for an all-RCBO board then there will be space in there for an all-RCBO arrangement. You'll need an RCBO for each of the "ways", also you'll need a new full-width busbar, the existing one will have been chopped up into (at least) two pieces.