Thank you.
What about 2 on the hive (heating off)
So far I understand it to be
N to N
L to L
Common (1 on hive ) to room stat out
Heating on (3) to room stat in
The diagram on the hive box says I need
Permanent neutral (got that)
Permanent live (got that)
Common (now know that goes to stat out)
Heating off NC (haven't got this yet)
Heating on NO (room stat in)
So do I need the heating off NC thing ??
Thank you once again and I'll happily post the screen shot.... be worth it as the wife will stop nagging
Seriously. I really appreciate your help
No Heating Off is not required. once Hive decides its warm enough it will break the contact and turn demand off.
Have you wired it in yet?
Your above working is right just forget the NC (2) terminal
Jon