Hi All,
hopefully a quick question for you all.
ok my oven supply is 10mm cable.
I currently only have one double oven that is rated at 4.2kw. I’m looking at replacing with two single ovens and a induction hob to an island. New ovens are 3.2kw each and hob is 7.4kw. Breaker had been upgraded to 50a.
I have purchased the dual appliance outlet so 10mm into the top and then connect the two ovens to each of the dual outlets.
two questions. Firstly can I use 2.5mm flex cable on each oven and secondly can I connect a 6mm supply cable to the same dual outlet plate to supply the island and add additional dual outlet plate to Island to supply induction hob.
I have asked something similar before but just want clarification on cable sizes and if this is acceptable.
Thanks all