Existing installation.
9.5kW shower
6mm cable
40A RCBO
Has worked ok since installed 2 years back.
Recent issue with circuit tripping.
Sparky identified faulty wiring in the isolator switch, switch replaced.
Sparky has advised it should be on a 32A RCBO.
Checking the shower installation manual, it states 40/45A MCB for their 9.5kW model, however if running on a 6mm cable they further state circuit protection should be 32A. So that's why he's suggesting a 32A RCBO?
I'm assuming best practice would have been 10mm cable, however shower was installed by plumber as a replacement during refurb so he'll just have used the existing cable.
If the 6mm cable's to remain in-situ, do you agree re dropping to 32A RCBO?