Hello
I’m wondering if I’ve made a mistake here. I’ve got a 40mm shower waste outlet which runs less than a metre horizontally before it drops vertically for 2.5m, then goes outside for a further 2m horizontal run to the soil stack.
I see regs say anything over 3m should be 50mm but does that include the vertical run too?
It’s not too late to change but I’d prefer not to! Thanks.