To get back to your problem, from 26 Nov to 26 Dec 2024 I used 208 m3 gas (heating, hot water and hob). My house isn't particularly well insulated and I leave it on 24/7.Thanks so much, this at least lets me know it's not wildly out for the property.
I will have to look at getting cavity wall insulation done soon and other measures.
Your figures don't sound right. Does your smart meter have an instantaneous flow reading, or a volume reading which you could take over a timed interval to get flow? Then you can set the boiler at maximum output, and compare the reading with the actual boiler consumption, about 3 m3/h for 30kW output.