I have only had one bath in this house, we use the shower, so although we have two baths, they are not used, so having more than a bowl full of water heated at first thought, seems pointless, but we had an 11-inch immersion heater, and we would run out of hot water, mainly as no sun that day, so went to 27-inch immersion heater, and not run out since, it can now last a few days.
The Willis one assumes can heat whole tank, but what I am not sure about is what will happen with 200 watt rather than 3000 watt? I can read about stratification as much as I want, but that does not explain speed of circulation, and how it can or can't use free energy to heat up water, well not quite free, as would get paid 12p/kWh if not used to heat the water.
Over or under 4°C water expands, so gets lighter, so will raise, and we want stored water either cold, or above 60°C, so we want the Epilimnion (top) to be at 60°C or higher, and the Hypolimnion (bottom) to be cold, and the Metalimnion layer as small as possible, there are loads on the internet about Stratification, and the layer in a pond or sea, but as to Stratification in a tank.
With heat pumps not being really hot enough, the idea of the immersion heater is returning. Is it really worth all the valves and system to get the water hotter for when heating DHW? When our CH was above 60°C it was not a problem, but with heat pumps, most of the time the circulating water is too cool, and I found the statement that it's cheaper to use the CH boiler to get DHW is a myth, there may be cases where it is, but also many cases where it's not.
To run a 35 kW boiler to get 2 pints of water to wash one's hands, has to be daft, 4 times as much energy goes into heating the heat exchangers in the boiler as what is used to heat the water that comes out of the tap. I find I used around 35 kWh in summer with the immersion heater and 7 kWh in winter every 28 days, in the summer I found my 20 kW boiler would run for around 20 minutes every other day and the water was a bit on the cool side, so used around 95 kWh per 28 days using oil. But that does not take into account any losses in the boiler. I have noticed a drop in oil use, since using the immersion heater.
But I have no way to really measure how much oil used with a 20 minute burn. And when I used gas, I had a modulating boiler, so again no real way to measure.
The Willis one assumes can heat whole tank, but what I am not sure about is what will happen with 200 watt rather than 3000 watt? I can read about stratification as much as I want, but that does not explain speed of circulation, and how it can or can't use free energy to heat up water, well not quite free, as would get paid 12p/kWh if not used to heat the water.
Over or under 4°C water expands, so gets lighter, so will raise, and we want stored water either cold, or above 60°C, so we want the Epilimnion (top) to be at 60°C or higher, and the Hypolimnion (bottom) to be cold, and the Metalimnion layer as small as possible, there are loads on the internet about Stratification, and the layer in a pond or sea, but as to Stratification in a tank.
Not the Willis as uses a pump. the page is interesting but does not really answer the questions.System type D – DHW storage cylinder with external plate heat exchanger and loading pump.
The DHW loading storage system enables the whole volume of the DHW to be heated to an even temperature throughout the tank by the use of a bronze pump that circulates the higher temperature throughout the whole cylinder. This system offers an increased amount of usable hot water compared to an equivalent volume of the water within system C, as the primary coil within system C experiences a reduction in heat exchanger effectiveness during the charging and discharging phase. This system increases the amount of available hot water whilst improving protection against the risks of legionella by avoiding cold spots between 20 and 45°C within the cylinder.
TIP: Ask the manufacturer for their pressure drop graph of their plate heat exchanger (HEX) and check the pressure drop across the HEX at the design flow rate against the available head of pressure of the primary pump. A 9 kW heat pump could deliver 26 litres per minute.
With heat pumps not being really hot enough, the idea of the immersion heater is returning. Is it really worth all the valves and system to get the water hotter for when heating DHW? When our CH was above 60°C it was not a problem, but with heat pumps, most of the time the circulating water is too cool, and I found the statement that it's cheaper to use the CH boiler to get DHW is a myth, there may be cases where it is, but also many cases where it's not.
To run a 35 kW boiler to get 2 pints of water to wash one's hands, has to be daft, 4 times as much energy goes into heating the heat exchangers in the boiler as what is used to heat the water that comes out of the tap. I find I used around 35 kWh in summer with the immersion heater and 7 kWh in winter every 28 days, in the summer I found my 20 kW boiler would run for around 20 minutes every other day and the water was a bit on the cool side, so used around 95 kWh per 28 days using oil. But that does not take into account any losses in the boiler. I have noticed a drop in oil use, since using the immersion heater.
But I have no way to really measure how much oil used with a 20 minute burn. And when I used gas, I had a modulating boiler, so again no real way to measure.