Picture of the week!™

Joined
31 Mar 2006
Messages
20,030
Reaction score
1,396
Location
Leeds
Country
United Kingdom
Well folks, it's that time again!

This was taken in a commercial premises during a PIR.

Can anyone spot the problem?

I removed the covers. That is not it :wink:


IMGP2623.jpg
 
Took me ages to find that, because I didn't scroll over to the r/h/s of the image...D'oh!
 
Is there an earth to that metal enclosure feeding the SWA? Or is that a TT earthing arrangement from there onwards? If so, hope precautions have been taken against tail damage where the tails enter that metal enclosure!
 
studying at the moment to become an electrician and I do find these pictures of the week very interesting.

On this one the earth block appears to have a phase cable attached??
 
studying at the moment to become an electrician and I do find these pictures of the week very interesting.

On this one the earth block appears to have a phase cable attached??

That looks like the main earthing conductor from the leaded sheath of the incoming supply cable.
 
Is there an earth to that metal enclosure feeding the SWA?
Looks to me like there is an earth wrapping arround the bottom of the cupboard and then clipped along the SWA.
Yea, but that could either be a supplementary earth, or going out to an earth rod - There is no connection from that enclosure to the MET. Hence my question.
 
Is there an earth to that metal enclosure feeding the SWA?
Looks to me like there is an earth wrapping arround the bottom of the cupboard and then clipped along the SWA.
Yea, but that could either be a supplementary earth, or going out to an earth rod - There is no connection from that enclosure to the MET. Hence my question.



Can't resist this.... :lol: Sureley that g/y clipped to the armour IS the connection to the MET (the earth block). Its the MET because it connects the Earthing Conductor to the means of earthing - the sheath of the incoming supply, and also, apparently, the bonding conductors.
 
IMGP2624-1.jpg



The G/Y entering the bottom of the RCD enclosure is a 4.0mm² earth.

It goes from the MET to the RCD enclosure, where it is connected to the enclosure and the SWA.


There is a red cable connected into the MET. It is the main earthing conductor, which is a ~10.0mm² VIR cable sweated onto the incommer cable.
 

If you need to find a tradesperson to get your job done, please try our local search below, or if you are doing it yourself you can find suppliers local to you.

Select the supplier or trade you require, enter your location to begin your search.


Are you a trade or supplier? You can create your listing free at DIYnot Local

 
Back
Top