The main problem with fluorescent lights was the tight voltage range. Over the years we have seen voltage optimisers come and go to try and adjust the voltage.
I was working on the building of Sizewell 'B' and we had a ring of tunnels to put temporary lighting in. So the boss got some 110 volt 58 watt fluorescent fittings, and we did a quick calculation. Around ½ an amp each, 16 amp supply, so should power 32, but to be on safe side, we went with 25 on each string.
It tripped the MCB after ½ an hour, so we went to investigate, clamp-on ammeter was showing 20 amps, no wonder it tripped.
So next was some workshop tests, the units were really 230 volts, and it used an auto transformer to step up the supply voltage, this was marked 127-0-110 so we moved the input from 110 to 127 on the first 20 in the string, and this cured the problem.
The current dropped from 0.8 amps to 0.6 amps, so total dropped from 20 amps to 15 amps, and at 230 volts this is what the voltage optimiser did.
But then we moved from magnetic ballast to electronic. This adjusted for volt drop, and set the voltage just right, so a 58 watt tube was now using 56 watt, and it also improved the output and how long the tubes lasted, so with the same tube, the lumen per watt jumped from around 75-80 to 95-100 which when LED first came out, they could not equal. We were seeing LED lamps between 60 and 120 lumen per watt, the main problem was the way we had wired our homes.
AC can transfer using capacitive and inductive linking, so a DC lamps for a caravan could be 110 lumens per watt, but the AC lamp would flash unless some power is allowed to drain without lighting the lamp. So this anti-flash leakage is the same for a 2 watt or a 20 watt lamp, so the higher the wattage the better the lumens per watt. So a 22 watt LED fluorescent tube replacement can give 110 lumens per watt, where the fluorescent was only 100 lumens per watt. If the ballast is removed, otherwise the ballast uses some power, so the LED is only 95 lumens per watt.
But the LED has to allow for this waste of energy, so instead of 58 watt rated and around 5500 lumens, they are 22 watt and 2200 lumens. With the ballast 25 watt and 2200 lumens.
But, one often we used 58 watt fluorescent lamps to get the spread of light, and we did not need the 5500 lumens and can get away with 2200 lumens.
And to use a fluorescent fitting, with a LED lamp, means easy to replace the lamp when it fails. Oh, and with an electronic ballast LED and Fluorescent tubes last about the same time.
Designing a LED tube with a switch mode power supply built in so it can run between 130 and 250 volts is easy enough, but to design one to work on the output of another switch mode power supply, at kHz, is not so easy, so the electronic ballast has to be removed.